The RSIC-DC04X2 is a 72 lb double-isolator connector used to resiliently attach secondary wall framing, suspended ceiling framing or selected mechanical/equipment supports to the primary structure. The two isolated mounting ferrules attach to the structure, while the projecting steel blade provides the decoupled connection point. It is used on walls and ceilings in new construction or retrofit; it is not an RSIC-1-style hat-channel clip, and drywall never fastens through its rubber isolators.

  • Two isolated mounting points: Two structural fasteners pass through the connector's internal metal ferrules into wood, steel, concrete or CMU. The ferrules must seat firmly against the structure.
  • Projecting steel blade: The vertical blade — minimum 4-1/2 in projection from the supporting structure per PAC's current submittal — carries the isolated connection: secondary framing, minimum 12 ga hanger wire through the existing 1/4 in hole, or a specifically designed equipment attachment.
  • 72 lb acoustical design load: Maximum dead or shear acoustical design load of 72 lb per connector, with 3 mm total listed deflection and double deflection per PAC's submittal. The separate RSIC-DC04X2 HD is the 144 lb version.
  • Walls and ceilings, new or retrofit: PAC lists use on walls and ceilings, in new construction and retrofit. Layout differs by application: connectors no more than 48 in apart on each vertical stud for framing, or a maximum 48 in × 48 in grid for ceilings.
$14.59
/ clip

Online orders up to 4,999 pieces. For anything larger, call (415) 864-4440 and we'll price the project with you.

Volume pricing

$14.59 per clip. Order 250+ clips and pay $14.34 per clip — an extra $0.25 off per clip for each additional 250 clips, down to a $12.29 per clip floor.

Discounts apply automatically in the cart and count boxes and cases toward the total.

Authorized PAC International DealerStandard 72 lb X2 — HD version sold separatelyLocal pickup: SF, San Leandro, LA
Product Specs

RSIC-DC04X2 Specifications

Product type
Double-isolator decoupling connector (not a drywall or hat-channel clip)
Acoustical design load
72 lb dead or shear, per connector
Total deflection
3 mm · double deflection (PAC submittal)
Blade projection
4-1/2 in minimum from supporting structure to end of blade
Cavity
Minimum 4-1/2 in · maximum and adjustment listed as variable
Overall height
4-1/2 in
Blade / face width
1-1/2 in on the submittal drawing (install guide lists 1-3/4 in overall width)
Base span across both isolators
3-1/2 in
Structure attachment
Two fasteners through the two internal ferrules
Max layout — walls
Connectors no more than 48 in apart on each vertical stud
Max layout — ceilings
48 in × 48 in on center
Minimum steel framing
20 ga (0.030 in)
Use on walls / ceilings
Yes / Yes · new construction and retrofit
Companion Component

Attachment fasteners

Wood framing
Two #10 × 2-1/2 in minimum, Type W coarse thread
Steel framing
Two #10 × 1-5/8 in minimum, Type S fine thread
Concrete / CMU
Two anchors, 2 in minimum length, #10 minimum shank or greater
Anchor length
Required embedment plus 1 in for the internal ferrule
Per-fastener capacity
Minimum 36 lb allowable pullout and shear (standard X2)
Nails
Never — approved screws or anchors only
Connector Estimator

RSIC-DC04X2 Preliminary Estimate

Gypsum does not fasten through this connector, so the count never comes off drywall area. On walls, PAC allows connectors no farther than 48 in apart on each vertical stud when isolating framing. On ceilings, the connector grid is a maximum of 48 in × 48 in on center. Pick the connection you are estimating.

Connectors are counted on the secondary studs that actually receive them, with enough rows that spacing along every stud stays within 48 in. First and last positions and any end restraint follow the wall and framing design. Connectors are fastened, not cut — the percentage above is an optional jobsite spare allowance, not cut waste.

Preliminary Material Estimate
Connectors (with spares)51
Layout before spares48 connectors
Secondary studs per section16
Connectors per stud3 · about 36 in apart
Structure fasteners (2 per connector)102
Sanity check — area ÷ 5.33 sq ft180 sq ft → 34
Preliminary material estimate — not a final structural, seismic, equipment-support or acoustical design. Each connector is limited to a 72 lb dead or shear acoustical design load, and quantity has to satisfy the predicted connection forces as well as the spacing maximums. PAC's guide specification requires the contractor to submit the proposed layout to the manufacturer and the architect.
Product Comparison

How RSIC-DC04X2 compares

ModelIsolatorsAcoustical Design LoadWhat Attaches To ItMaximum Layout
RSIC-DC04X2thisTwo72 lb per connectorSecondary framing, 12 ga hanger wire / drywall grid, designed equipment support48 in along each vertical stud · 48 in × 48 in ceiling grid
RSIC-DC04One36 lb per connectorSecondary framing or suspended components, per its own guidePer the RSIC-DC04 installation guide
RSIC-DC04X2 HDTwo — heavy duty144 lb per connector (2024 guide specification)Same connections, heavier loads48 in × 48 in ceiling grid · 48 in along each vertical stud
RSIC-1One molded rubber isolatorPer its own guide7/8 in furring channel, which then carries gypsumPer the RSIC-1 installation guide
Downloads

Data Sheets & Guides

PAC Clips — Data Sheets Library
FAQ

RSIC-DC04X2 — Common Questions

No. Two structural fasteners pass through the connector's internal ferrules into the primary structure, and the projecting steel blade takes the isolated connection — secondary framing, hanger wire for a drywall grid, or a specifically designed equipment support. Gypsum is then installed on that secondary framing or on a separately specified ceiling/wall system.