The Resilmount A50R is a rubber sound isolation hanger for internal wire-suspended ceilings. It fits in series between two sections of minimum 12-gauge hanger wire: the upper wire drops from the approved overhead structure, the lower wire continues down to the ceiling suspension clip and drywall or acoustical grid, and the rubber element in between decouples the finished ceiling from the structure. It is made for suspended ceilings, not for wall assemblies.

  • Installed in series on hanger wire: A minimum 12-gauge upper wire is bent or hooked through the top of the hanger per the ceiling-system manufacturer, and a separate minimum 12-gauge lower wire carries on to the suspension clip and grid.
  • Three capacities, colour coded: A50R-1 (Red) 65 lb, A50R-2 (Black) 120 lb and A50R-3 (Blue) 200 lb. All are about 4 in high and give 3/16 in maximum deflection at their stated maximum weight.
  • Capacity comes from the real load: Work out the complete ceiling mass carried at each hanger, then apply Resilmount's recommended 10-20% margin when selecting capacity. That margin is about which model you pick — it does not add hangers.
  • Spacing set by the number of board layers: One layer of 5/8 in gypsum allows a maximum 48 x 48 in grid; two layers tighten it to 48 x 24 in. Perimeter hangers sit 6 in from the wall.
  • Works with the specified grid system: The hanger wires connect it to whatever compatible suspended drywall or acoustical grid the project specifies — no proprietary channel connection at the hanger itself.
$14.99
/ hanger

Online orders up to 4,999 pieces. For anything larger, call (415) 864-4440 and we'll price the project with you.

Authorized Resilmount DealerCeiling-only wire-suspended isolation hangerLocal pickup: SF, San Leandro, LA
Product Specs

A50R Specifications

Capacity must be confirmed
The listed single and box options do not yet select a capacity — confirm A50R-1, A50R-2 or A50R-3 with our team before your order is processed
Use on ceilings
Yes — internal wire-suspended drywall or acoustical ceilings
Use on walls
No — the A50R is not intended for wall assemblies
A50R-1 (Red)
65 lb capacity · durometer 50 (+/- 5)
A50R-2 (Black)
120 lb capacity · durometer 68 (+/- 5)
A50R-3 (Blue)
200 lb capacity · durometer 80 (+/- 5)
Deflection
3/16 in maximum (static) deflection at the stated maximum weight
Height
Approximately 4 in, all three models
Upper connection
Minimum 12-gauge hanger wire, bent or hooked per the ceiling-system manufacturer
Lower connection
Separate minimum 12-gauge hanger wire inserted and bent through the lower side, continuing to the ceiling suspension clip and grid
Not a direct connection
No 3/8 in all-thread, threaded rod, hat/furring channel or CRC connects to the hanger itself
Maximum spacing — one layer 5/8 in gypsum
48 x 48 in o.c.
Maximum spacing — two layers 5/8 in gypsum
48 x 24 in o.c.
Perimeter hangers
6 in from the wall
Estimating weights
5/8 in gypsum 2.2 lb/sq ft · 1/2 in gypsum 1.6 lb/sq ft, plus grid, insulation, lights and other permitted loads
Capacity selection margin
Resilmount recommends increasing the calculated ceiling mass by 10-20% when selecting capacity
Perimeter detail
1/8-1/4 in gypsum perimeter gap filled with acoustical caulk
Companion Component

Making the connection

1 — Structure
Approved overhead structure and anchors. Anchors and any hanger bracket are separate, project-specific hardware — the written instructions recommend an M47 bracket while the submittal package also references M100, so follow the current approved detail for your project
2 — Upper hanger wire
Minimum 12-gauge hanger wire, bent or hooked per the ceiling-system manufacturer
3 — A50R hanger
The rubber isolation hanger, in series between the two wires, at the rated capacity for that location
4 — Lower hanger wire
Separate minimum 12-gauge hanger wire inserted and bent through the lower side
5 — Suspension clip and grid
Ceiling suspension clip and the specified drywall or acoustical grid
6 — Finished ceiling
Gypsum board with a 1/8-1/4 in perimeter gap filled with acoustical caulk
Hanger Estimator

A50R Preliminary Ceiling Estimate

For internal wire-suspended ceilings. One A50R sits in series between an upper and a lower minimum 12 ga hanger wire at each designed hanger location, so the count is the hanger grid on the reflected ceiling plan. Resilmount's maximum spacing is 48 x 48 in o.c. with one layer of 5/8 in gypsum and 48 x 24 in o.c. with two layers, with perimeter hangers 6 in from the wall.

Capacity is selected, not guessed
  • A50R-1 (Red) — 65 lb capacity, durometer 50 (+/- 5), about 4 in high, 3/16 in maximum deflection at its stated maximum weight.
  • A50R-2 (Black) — 120 lb capacity, durometer 68 (+/- 5), about 4 in high, 3/16 in maximum deflection at its stated maximum weight.
  • A50R-3 (Blue) — 200 lb capacity, durometer 80 (+/- 5), about 4 in high, 3/16 in maximum deflection at its stated maximum weight.

Resilmount recommends increasing the calculated ceiling mass by 10-20% when choosing capacity. That margin applies to the load you select against — it does not add hangers and it is not a product waste allowance. Correct deflection and load distribution still require engineering review or Resilmount selection; do not simply pick the largest model.

How many, in plain terms

Total hangers = hanger rows x hanger columns from the reflected ceiling and grid plan. A rough area check is one hanger per 16 sq ft with a single layer and one per 8 sq ft with two layers, but 6 in perimeter offsets and the real grid always raise that number. No 10% waste allowance and no seismic buffer are added to a hanger count.

Example — 20 ft x 16 ft ceiling (preliminary)

One layer: the area check is 320 / 16 = 20, but with 6 in perimeter offsets and spacing no greater than 48 in the plotted grid is about 6 x 5 = 30 hangers. Two layers: the area check is 320 / 8 = 40, while a 24 x 48 in grid with the same offsets works out to roughly 54–55 hangers depending on orientation and rounding. Both are planning numbers — count the actual grid.

Worked load example

On a 4 ft x 4 ft tributary area, one layer of 5/8 in gypsum alone is 16 sq ft x 2.2 lb = 35.2 lb before the grid, insulation and lights are added. Add every one of those weights, apply the 10-20% selection margin, then choose the model whose capacity covers the approved total. With two layers, use the specified 24 x 48 in tributary grid (8 sq ft) rather than loading a hanger with 16 sq ft of doubled board.

Preliminary material takeoff only. Anchors, hanger brackets and any seismic or lateral bracing are separate, project-specific overhead hardware — follow the current approved Resilmount detail, the project drawings and code, and never let bracing short-circuit the isolated ceiling. Confirm the A50R capacity (A50R-1, -2 or -3) with our team before ordering.

Product Comparison

How A50R compares

ModelPrimary useUpper connectionLower connectionMaximum spacing
A50RthisCeilings only — internal wire-suspended ceilingsMinimum 12-gauge hanger wire from the approved structureMinimum 12-gauge hanger wire to the suspension clip and grid48 x 48 in (one layer) · 48 x 24 in (two layers)
A72RCeilings — resilient bracket carrying a hanger wireFastened to the structure per its own instructionsMinimum 12-gauge hanger wire to a suspended drywall gridPer the A72R installation instructions
A237CRCeilings — cold-rolled-channel to furring-channel clipLocks over 1-1/2 x 1/2 in, 16 ga cold-rolled channelFurring channel in a resilient two-step lockOne clip per CRC / furring crossing
Downloads

Data Sheets & Guides

Resilmount — A50R sound isolation hanger product page
FAQ

A50R — Common Questions

Use it on internal wire-suspended ceiling systems that call for a rubber isolation hanger in one of the three published capacities. Do not use it on walls, in direct clip-to-hat construction, in a direct rod or channel connection without an approved detail, in exterior environments, or to carry heavy services — those must be supported independently of the isolated ceiling.